Two-Position Control
Two-position control compares the value of an analog or variable
input with instructions and generates a digital (two-position) output. The
instructions involve the definition of an upper and lower limit. The output
changes its value as the input crosses these limit values. There are no
standards for defining these limits. The most common terminology used is
setpoint and differential. The setpoint indicates the point where the output
“pulls-in,” “energizes” or is “true.” The output changes back or “drops-out”
after the input value crosses through the value equal to the difference between
the setpoint and the differential.
Two-position control can be used for simple control loops
(temperature control) or limit control (freezestats, outside air temperature
limits). The analog value can be any measured variable including temperature,
relative humidity, pressure, current and liquid levels.
Time can also be the input to a two-position control response. This
control response functions like a time clock with pins. The output “pulls-in”
when the time is in the defined “on” time and drops out during the defined
“off” time.

Figure 3, shows an example of two-position control in a home
heating system, where the thermostat is set to energize the heating system when
the space temperature falls below 70° F and turn off when the temperature rises
to 72° F in the space. This is an example of a setpoint of 70° F with a
two-degree differential.
Floating Control
Floating control is a control response that produces two possible digital
outputs based on a change in a variable input. One output increases the signal
to the controlled device, while the other output decreases the signal to the
controlled device. This control response also involves an upper and lower limit
with the output changing as the variable input crosses these limits. Again,
there are no standards for defining these limits, but the terms setpoint and
deadband are common. The setpoint sets a midpoint and the deadband sets the
difference between the upper and lower limits.
When the measured variable is within the deadband or neutral zone,
neither output is energized and the controlled device does not change - it
stays in its last position. For this control response to be stable, the sensor
must sense the effect of the controlled device movement very rapidly. Floating
control does not function well where there is significant thermodynamic lag in
the control loop. Fast airside control loops respond well to floating control.
An example of floating controls is shown in Figure 4.

Proportional Control
A proportional control response produces an analog or variable output change in
proportion to a varying input. In this control response, there is a linear
relationship between the input and the output. A setpoint, throttling range and
action typically define this relationship. In a proportional control response,
there is a unique value of the measured variable that corresponds to full
travel of the controlled device and a unique value that corresponds to zero
travel on the controlled device. The change in the measured variable that
causes the controlled device to move from fully closed to fully open is called
the throttling range. It is within this range that the control loop will
control, assuming that the system has the capacity to meet the requirements.
The action dictates the slope of the control response. In a direct
acting proportional control response, the output will rise with an increase in
the measured variable. In a reverse acting response, the output will decrease
as the measured variable increases. The setpoint is an instruction to the
control loop and corresponds to a specified value of the controlled device,
usually half-travel. An example is shown in Figure 5.

In a proportional control system, the value of the measured
variable at any given moment is called the control point. Offset is defined as
the difference between the control point and the desired condition. One way to
reduce offset is to reduce throttling range. Reducing the throttling range too
far will lead to instability. The more quickly the sensor “feels” the effect of
the control response, the larger the throttling range has to be to produce
stable control.
Proportional plus
Integral (PI) Control
PI control involves the measurement of the offset or “error” over time. This
error is integrated and a final adjustment is made to the output signal from
the proportional part of this model. This type of control response will use the
control loop to reduce the offset to zero. A well set-up PI control loop will
operate in a narrow band close to the setpoint. It will not operate over the
entire throttling range (Figure 6).

PI control loops do not perform well when setpoints are dynamic,
where sudden load changes occur or if the throttling range is small.
Proportional plus Integral plus
Derivative (PID) Control
PID control adds a predictive element to the control response.
In addition to the proportional and integral calculation, the derivative or
slope of the control response will be computed. This calculation will have the
effect of dampening a control response that is returning to setpoint so quickly
that it will “overshoot” the setpoint.
PID is a precision process control response and is not always
required for HVAC applications. The routine application of PID control to every
control loop is labor intensive and its application should be selective.
Definition of Direct Digital Control
(DDC)
DDC control consists of microprocessor-based controllers with
the control logic performed by software. Analog-to-Digital (A/D) converters
transform analog values into digital signals that a microprocessor can use.
Analog sensors can be resistance, voltage or current generators. Most systems
distribute the software to remote controllers to eliminate the need for
continuous communication capability (stand-alone). The computer is primarily
used to monitor the status of the energy management system, store back-up
copies of the programs and record alarming and trending functions. Complex
strategies and energy management functions are readily available at the lowest
level in the system architecture. If pneumatic actuation is required, it is
accomplished with electronic to pneumatic transducers. Calibration of sensors
is mathematical; consequently the total man-hours for calibration are greatly
reduced. The central diagnostic capabilities are a significant asset. Software
and programming are constantly improving, becoming increasingly user-friendly
with each update.
Benefits of DDC
The benefits of direct digital control over past control
technologies (pneumatic or distributed electronic) is that it improves the
control effectiveness and increases the control efficiency. The three main
direct benefits of DDC are improved effectiveness, improved operation
efficiency and increased energy efficiency.
Improved Effectiveness
DDC provides more effective control of HVAC systems by providing
the potential for more accurately sensed data. Electronic sensors for measuring
the common HVAC parameters of temperature, humidity and pressure are inherently
more accurate than their pneumatic predecessors. Since the logic of a control
loop is now included in the software, this logic can be readily changed. In
this sense, DDC is far more flexible in changing reset schedules, setpoints and
the overall control logic. Users are apt to apply more complex strategies,
implement energy saving features and optimize their system performance since
there is less cost associated with these changes than there would be when the
logic is distributed to individual components. This of course assumes the user
possesses the knowledge to make the changes.
DDC systems, by their very nature can integrate more easily into
other computer-based systems. DDC systems can integrate into fire control
systems, access/security control systems, lighting control systems and
maintenance management systems.
Improved Operational Efficiency
Operational improvements show the greatest opportunity for
efficiency improvements in direct digital controls. The alarming capabilities
are strong and most systems have the ability to route alarms to various
locations on a given network. The trending capabilities allow a diagnostic
technician or engineer to troubleshoot system and control problems. They also
allow the data to be visualized in various formats. These data can also be
stored and analyzed for trends in equipment’s performance over time.
Run-times of various equipment can be monitored and alarms/messages
can be generated when a lead/lag changeover occurs or if it is time to conduct
routine maintenance.
The off-site access/communication capability allows an
owner/operator to access their system remotely. Multiple parties can also be
involved in troubleshooting a problem. The control vendor, design engineer and
commissioning authority can use these features to more efficiently diagnose and
visualize problems.
Increased Energy Efficiency
There are many energy-efficient control strategies employed in
pneumatic logic that can be easily duplicated in DDC logic. Due to the addition
of more complex mathmatical functions (easily obtained in software), there are
many additional energy-efficient routines that can be used with DDC.
Strategies such as demand monitoring and limiting can be more
easily implemented with DDC systems. The overall demand to a facility can be
monitored and controlled by resetting various system setpoints based on
different demand levels. If a DDC system is installed at the zone level, this
could be accomplished by decreasing the requirement for cooling on a
zone-by-zone basis.
By storing trends, energy consumption patterns can be monitored.
Equipment can also be centrally scheduled “on” or “off” in applications where
schedules frequently change.
Continue To Chapter 3
|