Analog Inputs The analog signals generated by some types of sensors must be conditioned by converting to a higher-level standard signal that can be transmitted over wires to the receiving controller. Analog inputs are converted to digital signals by the analog-to-digital (A/D) converter typically located at the controller. Analog-to-digital conversion is limited to a small range of DC voltage, so that internal or external input circuitry must change the character of non-compatible signal types to a DC voltage range within the limits of the A/D converter. Common Types Voltage Current Resistance Circuit Diagrams
Figure 4 shows a voltage input circuit where the sensor output voltage does not match the controller.
Figure 5 shows the wiring schematic associated with a typical externally powered 4-20 mA analog input using a loop power 4-20 mA temperature transmitter. For this circuit type, typical power supply voltage is nominally 24 VDC. The circuitry in the transmitter regulates current flow in the loop between 4 and 20 mA in proportion to the temperature sensed by the sensor. A parallel fixed resistor is used at the controller terminals to complete the circuit. The resistance of the A/D converter in the circuit is very high in comparison to R, essentially all of the current flows through the resistor. The value of the resistor is chosen to match the input voltage range of the controller.
Figure 6 depicts the circuit for converting a resistance
to voltage, in this case, a 10 kW Thermistor-type
sensor. Continue on to Chapter 1: Analog Outputs
|
|||||||||||||